Refrigerant leak detector types: capability and limits

Compare infrared, heated-diode, ultrasonic and bubble leak detection without confusing sensitivity, refrigerant support and safe use.

DIRECT ANSWER

Choose a method for the refrigerant, environment and question being asked. Refrigerant-sensitive electronic detectors, ultrasonic instruments and approved bubble solutions detect different effects. A sensitivity figure or a refrigerant-table entry does not establish suitability for every refrigerant or approval for a flammable atmosphere.

Source-based explanation

Four methods, four kinds of evidence

MethodDetected effectMain limits to check
InfraredAbsorption in sensor-specific infrared bandsNamed refrigerants, response, contamination and environmental limits; not every gas is detectable
Heated diodeSensor response associated with specified refrigerants, commonly halogen-containing gasesSensor ageing, contamination and gas coverage; do not assume a response to pure hydrocarbons
UltrasonicHigh-frequency sound associated with gas flowPressure difference, leak geometry, background noise and access; it does not identify the gas
Leak-detection solutionVisible bubble formation at an accessible leak pathSurface access, solution/material compatibility, temperature and suitable conditions

No method is a blanket substitute for the method required by the equipment procedure or applicable leak-check obligations. A negative indication means no indication under that setup; it is not proof that every possible leak path is absent.

Sensitivity units cannot be swapped

A stated minimum leak rate in grams per year is a mass flow under specified test conditions. Parts per million is a concentration at a location. Air movement, distance, sampling and refrigerant properties affect the relationship. There is no universal direct conversion between the two.

Compare a detector’s named test refrigerant and method, response time, warm-up, probe maintenance and verification requirements alongside its sensitivity. A laboratory specification is not our measured performance on a windy or contaminated site.

Refrigerant support and safe use are separate

R32, hydrocarbon refrigerants and blends have different properties. A general “HFC”, “HFO” or “HC” marketing label is insufficient to establish an exact model’s refrigerant list and safe-use conditions. Obtain the current manual and any required approvals for the refrigerant and environment. A refrigerant leak detector is not automatically a personal flammable-gas safety monitor.

A UV lamp is an illumination source; any fluorescent-dye method also depends on a permitted dye already present in an appropriate system. It does not make the electronic sensor sensitive to additional refrigerants.

Function checks and records

Record the detector model, serial number, sensor age, filter condition, warm-up status, sensitivity setting and the manufacturer-specified function-check result. Use an appropriate documented reference leak where required. A response to an improvised gas source is not a traceable calibration or a verified minimum leak rate.

UK applicability

Great Britain: check the current GOV.UK qualification and leak-check guidance for the activity and equipment. Northern Ireland: check DAERA’s separate F-gas guidance; do not assume the GB regime applies. Instrument ownership or an App report is not evidence of competence or legal compliance. These explanations do not provide charging, pressure-testing or flammable-refrigerant work instructions.

Sources and limits

References checked on . Manufacturer declarations and other authors’ observations are not our physical test results.

  1. ElitechEU: refrigerant leak detector comparison ↗

    Manufacturer specifications; generic refrigerant-family labels do not prove approval for an individual refrigerant.

  2. AC Service Tech: ultrasonic leak detection ↗

    Educator with commercial links; capability explanation, not our comparative test.

  3. GOV.UK: checking F gas equipment for leaks ↗

    Official leak-check guidance; do not infer applicability from a tool specification.

  4. GOV.UK: qualifications to work with F gas ↗

    Current official guidance; follow its territorial scope and activity-specific requirements.

  5. DAERA: fluorinated greenhouse gases in Northern Ireland ↗

    Northern Ireland authority; consult the separate NI regime and linked current guidance.

Keep the evidence with the reading

Use the blank field record for conditions, instruments, connection details and repeated readings. See how we assess evidence and our commercial relationship.

RELATED READING